Component Identification and Description of Operation
- 18 - IQ SERIES OWNERS MANUAL
Figure 3 Programming Switch Instruction Label
2.18 (18) PROGRAMMING CONTROL SWITCHES
IQ Models (Inverter only) Only Switch 2 is functional
Switch 2 allows Load Demand to be turned ON or OFF.
IQC Models (Inverter/Charger)
All positions of the Programming Switch are functional on IQC Models.
Switch# Position Left / Right Function
10 Add 64 amps / 0 Switches 7 through 10 add to set the bulk charge rate.
9 Add 32 amps / 0
8 Add 16 amps / 0
7 Add 8 amps / 0
6 90VAC / 77VAC Low AC Input Voltage switchover tolerance value.
5 Disable / Enable Disable Inverter operation. While the inverter is disabled the
battery charger and transfer switch remain operational.
4 Disable / Enable Disable Charger operation. The charger will be disabled only if
the inverter is also disabled at dip switch 5. The transfer switch
remains operational.
3 Start / Off Equalize Start
2 Enable / Disable Load Demand
1 Gel / Wet Battery Type
TO PREVENT BATTERY DAMAGE AND ASSURE
DESIRED SYSTEM OPERATION CONSULT
OWNERS MANUAL CONTROL PANEL SECTION
FOR PROPER CONTROL SETTINGS
*CAUTION
* B ATTE RY T YP E (POS. 1) :
GEL: GEL LEAD ACID BATTERY TYPE
WET: WET (FLOODED) LEAD ACID BATTERY TYPE.
LOAD TYP E (PO S. 2) :
* EQUA LIZ E (POS. 3 ):
OP EN SWIT CH (P OS. 4) :
*INVERT ER (POS. 5) :
*B ROW N OUT ( POS. 6 ):
ON: LOAD DEMAND ENABLED/AUTOMATIC.
OFF: LOAD DEMAND DISABLED.
EQUALIZE MODE SHOULD BE IN THE "OFF"
POSITION AS A STANDARD OPERATING MODE. IF BATTERIES
NEED TO BE EQUALIZED, SET SWITCH TO THE "ON" POSITION
THEN BACK TO THE "OFF" POSITION. THIS WILL INITIATE
EQUALIZE FOR ONE CYCLE. IF LEFT IN THE "ON" POSITION
BATTERIES COULD BE DAMAGED.
NOTE:
DEFAULT SETTING IS "B" POSITION.
INVERTER DISABLED. CHARGER AND AC TRANSFER
SWITCH WILL OPERATE.
OFF=
INVERTER ENABLED.ON=
HI=
LOW=
UNIT SWITCHES TO INVERTER MODE WHEN AC INPUT DROPS
BELOW 90VAC (199VAC ON 50HZ)
UNIT SWITCHES TO INVERTER MODE WHEN AC INPUT DROPS
BELOW 77VAC (190VAC ON 50HZ)
CONTROL SWITCH SETTINGS
* = INDICATED FEATURES USED ON CHARGER MODELS ONLY (IQC/IQCE)
CHARGER OUTPUT SETTINGS
AC OUTPUT
DC VOLTAGE
A (POS. 10)
B (POS. 9)
C (POS. 8)
D (POS. 7)
MAX AMPS
12 VDC
64A
32A
16A
8A
120A
24 VDC
32A
16A
8A
4A
60A
12 VDC
32A
16A
8A
4A
60A
24 VDC
16A
8A
4A
2A
30A
2600W OR 3600W 1800W
D07806-D
10
9
8
7
6
5
4
3
2
1
S2
A
B
C
D
CHA RG ER
OUT PUT
AM PS
ON O FF
HI
OFF
A
ON
ON
GEL
LOW
ON
B
OFF
OFF
WET
BR OWN OUT
INVERTER
OP EN S WIT CH
EQUA LIZE
LOAD DEMAN D
BAT T ERY TYPE
APM (N/A ON 50H Z)
BA TTER Y TEMP.
RE MOT E
J8
J1
J9