RE Installation Manual
4-22
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
d.
The "Charge Setting" is "28.40 Vdc" (
56.8 V
DC
for the
RE48-4500
) the same as the end point of the last stage.
Press the Top Right Key.
e.
The "Trigger Type" is "<DC CURRENT." Press the
Top Right Key.
f.
The "Trigger Settng" is "55.0 Adc."
(27.5 Adc for the
RE48-4500)
Press the Top Right Key.
g.
And last, the "Charge Timeout" is "1.00 Hours." Press
the Top Right Key to take you back to “Charge Step
#”.
During this third charging stage, the inverter/charger will
hold the voltage across the batteries at 28.40 Vdc (
56.8
Vdc for the RE48-4500
). The Inverter will do this until the
current into the batteries drops to below 55 amps
(27.5
Adc for the RE48-4500)
or until an hour has gone by and
then go on to the next charging stage.
4.
Perform the fourth set of charging steps:
a.
Set "Charge Step #" to 4. (The fourth charging stage)
Press the Top Right Key.
b.
The "Charge Stage " is "ABRB" standing for
absorption. Press the Top Right Key.
c.
The "Charge Type" is "DC CURRENT." Press the Top
Right Key.
d.
The "Charge Setting" is "50.0 Adc." (
25.0 Adc
for the
RE48-4500) Press the Top Right Key.
e.
The "Trigger Type" is ">=DC VOLTAGE." Press the
Top Right Key.
f.
The "Trigger Settng" is "30.00 Vdc (
60 Vdc for the
RE48-4500
)." Press the Top Right Key.
g.
And last, the "Charge Timeout" is "0.25 Hours." Press
the Top Right Key to take you back to “Charge Step
#”.
During this fourth charging stage, the inverter/charger will
provide 50 amps (
25 amps
for the RE48-4500
) into the
batteries. The Inverter will continue to do this until the
battery’s voltage have risen to 30 volts or until 15 minutes
has gone by, at which time the inverter will then go to the
next charging stage.
5.
Perform the fifth set of charging steps: