Appendix C: Settings
D-3
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
Frequency Settings
SETTING NAME FACTORY VALUE DEFAULT VALUE
1st Frequency Bad Delay (UL1741) 5 Cycles 5 Cycles
2nd Frequency Bad Delay (UL1741) 1 Cycle 1 Cycle
Displayed Frequency Adjust 60000 60000
Frequency Good Delay 1 Cycle 1 Cycle
Generator Upper Capture Frequency 65.00 Hz 65.00 Hz
Generator Lower Capture Frequency 55.00 Hz 55.00 Hz
Generator Upper Lock Frequency 70.00 Hz 70.00 Hz
Generator Upper Lock Frequency 40.00 Hz 40.00 Hz
Stacking Phase Angle 0.00 degrees 0.00 degrees
Phaselock Detect Angle 2.00 degrees 2.00 degrees
Frequency Adjust 1060722150 1060722150
GridTie Frequency Adjust (not used) 1590728628 1590728628
Grid Interactive Upper Capture
Frequency
60.25 Hz 60.25 Hz
Grid Interactive Lower Capture
Frequency
59.75 Hz 59.75 Hz
Grid Interactive Upper Lock Frequency 60.50 Hz 60.50 Hz
Grid Interactive Lower Lock Frequency 59.30 Hz 59.30 Hz
Generator Good Timeout 1 S 90 S
Phaselock Bad Timeout 2 Cycles 2 Cycles
Temperature Settings
SETTING NAME FACTORY VALUE DEFAULT VALUE
High Temperature Shutdown 70.00 degrees C 70.00 degrees C
Low Temperature Shutdown -40.00 degrees C -40.00 degrees C
System Temperature Offset 0 0
System Temperature Gain 5005 5005
Maximum Fan Volts 12.20 Vdc 12.20 Vdc
Minimum Fan Volts 6.00 Vdc 6.00 Vdc
Fan Start Temperature 30.0 degrees C 30.0 degrees C
Fan Off Delay 61 S 61 S
Fan Calibration 3000 3000
Room Temperature Setting 35.0 degrees C 35.0 degrees C