the batteries increases to greater than 50 amps (
25 Adc
for
the RE48-4500
) or until an hour has gone by, after which
the inverter will then go on to the next charging stage.
Note:
The current when charging probably won't rise so
the only effective trigger is the timeout. This means the
batteries will be left on float for at least an hour before
going on to the next stage.
7.
Perform the seventh set of charging steps:
a.
Use the remote to set "Charge Step #" to 7. (The
seventh charging stage) Press the Top Right Key.
b.
"Charge Stage ," the charging stage name, is " END,"
obviously standing for "end." Press the Top Right
Key.
c.
The "Charge Type" is "DC VOLTAGE." Press the
Top Right Key.
d.
The "Charge Setting" is "26.40 Vdc," (
52.8 Vdc for the
RE48-4500
) like the previous stage. Press the Top
Right Key.
e.
The "Trigger Type" is ">DC CURRENT." Press the
Top Right Key.
f.
The "Trigger Settng" again is "50.00 Adc." (
25 Adc
for the RE48-4500
) Press the Top Right Key.
g.
And last, the "Charge Timeout" is "0.00 Hours." Press
the ESC Key to take you up the charging menu tree.
This last charge step is kind of a placeholder where the
batteries are left at float, forever.
Note:
The last step is a trigger to stop the generator if
"Generator Strt" is ON.