System Setup
4-23
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
a.
Set "Charge Step #" to 5. (The fifth charging stage)
Press the Top Right Key.
b.
The "Charge Stage " is "EQUL" standing for
equalization. Press the Top Right Key.
c.
The "Charge Type" is "DC VOLTAGE." Press the
Top Right Key.
d.
The "Charge Setting" is "31.00 Vdc." (
62 Vdc for the
RE48-4500
) Press the Top Right Key.
e.
The "Trigger Type" is "<DC CURRENT." Press the
Top Right Key.
f.
The "Trigger Settng" is "10.00 Adc." (
5 Adc for the
RE48-4500
) Press the Top Right Key.
g.
And last, the "Charge Timeout" is "0.25 Hours." Press
the Top Right Key to take you back to “Charge Step
#”.
During this, fifth equalization charging stage, the
inverter/charger will hold the battery voltage at 31 volts.
The inverter will continue to do this until the current into
the batteries falls to less than 10 amps or until 15 minutes
have gone by, after which the inverter will then go on to
the next charging stage.
6.
Perform the sixth set of charging steps:
a.
Set "Charge Step #" to 6. (The sixth charging stage)
Press the Top Right Key.
b.
The "Charge Stage " is "FLTV" standing for float
voltage. Press the Top Right Key.
c.
The "Charge Type" is "DC VOLTAGE." Press the
Top Right Key.
d.
The "Charge Setting" is "26.40 Vdc
." (52.8 Vdc for the
RE48-4500
) Press the Top Right Key.
e.
The "Trigger Type" is ">=DC CURRENT." Press the
Top Right Key.
f.
The "Trigger Settng" is "50.00 Adc." (
25 Adc for the
RE48-4500
) Press the Top Right Key.
g.
And last, the "Charge Timeout" is "1.00 Hours." Press
the Top Right Key to take you back to “Charge Step
#”.
During this sixth, float charging stage, the inverter/charger
will hold the battery voltage at 26.4 volts (
52.8 Vdc
for the
RE48-4500
). The inverter will do this until the current into
Vue de la page 58