RE Installation Manual
3-12
Copyright
2001 Phone: (614) 771-2718 RE-4500
Vanner Inc. FAX: 614-771-4904 Owners Manual
4282 Reynolds Dr. www.vanner.com Rev 01e
Hilliard Ohio 43026 RE-Installation_Manual_Rev01e 910157-A
INCORPORATED
INCORPORATEDINCORPORATED
INCORPORATED
L1
L1
L2
N
Bottom
RightLeft
N
L2
GND
AC IN
AC OUT
26 27
GND
28
29
Warning
Class 1 Wiring Methods Are To Be Used For Field Wiring
Connections To Terminals Of A Class 2 Circuit. It Is Also Extremely
Important To Observe A Physical Separation Between Class 1 And
Class 2 Circuits. Be Sure To Route Class 1 And Class 2 Wiring
Through Separate Knockouts And Conduits.
Terminal and Component Definitions
This section contains the descriptions of the connectors and
components called out in Figure 3-2 and 3-3.
(22) and (23) DC connections
Connect 24 or 48 volt DC (depending on your RE model)
positive and negative to the inverter’s flat DC terminals with
5/16 cap screws. Use 5/16 ring terminals or compression lugs.
For the
RE24-4500 use a #02286-08, JJN-400, 400A fast blow fuse
and 4/0 cable, and for the RE48-4500, use a #02286-03, JJN-200,
200A fast blow fuse
. This fuse is required by UL to be within 18
inches of the Battery Terminals on the battery string.
The wiring of your inverter installation should conform to the
National Electric Code (NEC) and any other state or local
codes in effect at the time of installation. These codes have
F 3 Figure 3-3: Inverter AC Raceway Connections