Grid Interact
on OFF
Grid Interact Menus
MENU
MENU
MENU
UL 1741 Delay
+ 30 1 Secs -
Grid Vlt Sttngs
Grid Frq Sttngs
Grid Voltage MENU
Grid Freq. MENU
Freq Good Dly
+ 1 Cycles -
Freq Bad Dly 2
+ 1 Cycles -
Freq Bad Dly 1
+ 5 Cycles -
Lower Freq #2
+ 59.3 0 Hz -
Upper Freq #2
+ 60.5 0 Hz -
Lower Freq #1
+ 59.7 5 Hz -
Upper Freq #1
+ 60.2 5 Hz -
AC Good Delay
+ 6 0 Cycles -
AC Bad Delay 1
+ 11 5 Cycles -
Lower Volts #3
+ 59. 8 Vrms -
Upper Volts #3
+ 420. 0 Vrms -
Lower Volts #2
+ 119. 8 Vrms -
Upper Volts #2
+ 328. 0 Vrms -
Lower Volts #1
+ 211. 8 Vrms -
Upper Volts #1
+ 264. 0 Vrms -
Load Support
+ 10.0 0 Arms -
AC Bad Delay 3
+ 0 Cycles -
AC Bad Delay 2
+ 0 Cycles -