L1-N OUT BROWN
L1 in current regulation mode (brown-out)
L2-N OUT BROWN
L2 in current regulation mode (brown-out)
L1 IN SURGING
L1 Coming up on APM limit
L2 IN SURGING
L2 Coming up on APM limit
L1 APM LIMIT
L1 is at APM Limit
L2 APM LIMIT
L2 is at APM Limit
Factory Settings 24 VDC Only!!
SETTING NAME FACTORY VALUE DEFAULT VALUE
EEPROM Version value value
Battery Settings
SETTING NAME FACTORY VALUE DEFAULT VALUE
Number of Cells 12 12
High Battery Shutdown 31.00 Vdc 31.00 Vdc
Low Battery Shutdown 21.00 Vdc 21.00 Vdc
Low Battery Warning 22.00 Vdc 22.00 Vdc
Battery Offset -239 -239
Battery Gain 12670 12670
Battery Temperature Coefficient -5.00 mV/degrees C/Cell -5.00 mV/degrees C/Cell
High Battery Shutdown Temperature 60.0 degrees C 60.0 degrees C
Battery Temperature Offset 0 0
Battery Temperature Gain 10240 10240
Battery Bad Delay 13 S 13 S
Battery Bad Temperature Delay 1 S 1 S